Image from Google Jackets

Evaluation of the Onset of Flashover in Room Fire Experiments

By: Language: Inglés Publication details: oct. 2013Description: 14 p. ; 891-905 In: Fire Technology 49Summary: Transcripción del resúmen realizada por el autor: Two series of full scale room fire tests comprising 16 experiments are used for a study of the onset of flashover. The fire loads were varied and represented seven different commercial applications and two non-combustible linings with significantly different thermal inertia were used. The test results showed that by lowering the thermal inertia and thereby lowering the heat loss from the room and at the same time increasing the thermal feedback, a thermal runaway occurred before significant fire spread; but only for objects composed of a mixture of plastic/rubber/textiles and wood/celluloses. In these cases the onset of thermal runaway was found to occur at room temperatures in the range 300°C to 420°C, supporting that the room temperature at the onset of thermal runaway is strongly dependent on the thermal inertia. It also shows that the onset of thermal runaway cannot in all cases implicitly be predicted by the traditional flashover temperature criterion of 500°C to 600°C. For fire loads composed of pure wood/celluloses the onset of flashover occurred about the same time as fire spread irrespectively of linings and at significantly higher room temperatures (725°C). This can be explained by flammability parameters making wood/celluloses less sensitive to thermal feedback.
Item type: Artículo de Revista
Holdings
Current library Status Barcode
Biblioteca Alejandro Angel Bulgheroni Not for loan 200060120

Transcripción del resúmen realizada por el autor: Two series of full scale room fire tests comprising 16 experiments are used for a study of the onset of flashover. The fire loads were varied and represented seven different commercial applications and two non-combustible linings with significantly different thermal inertia were used. The test results showed that by lowering the thermal inertia and thereby lowering the heat loss from the room and at the same time increasing the thermal feedback, a thermal runaway occurred before significant fire spread; but only for objects composed of a mixture of plastic/rubber/textiles and wood/celluloses. In these cases the onset of thermal runaway was found to occur at room temperatures in the range 300°C to 420°C, supporting that the room temperature at the onset of thermal runaway is strongly dependent on the thermal inertia. It also shows that the onset of thermal runaway cannot in all cases implicitly be predicted by the traditional flashover temperature criterion of 500°C to 600°C. For fire loads composed of pure wood/celluloses the onset of flashover occurred about the same time as fire spread irrespectively of linings and at significantly higher room temperatures (725°C). This can be explained by flammability parameters making wood/celluloses less sensitive to thermal feedback.

4



Instituto Argentino del Petróleo y del Gas
Maipú 639 (C1006ACG) – Buenos Aires – Argentina
Tel: (54 11) 5277 IAPG (4274)
Lu - Vie 11 a 17 hs
Mail: biblio@iapg.org.ar


Copyright © 2026, Instituto Argentino del Petróleo y del Gas, todos los derechos reservados.

Protección de datos personales