Evaluation of the Onset of Flashover in Room Fire Experiments (Record no. 187966)
[ view plain ]
| 000 -LEADER | |
|---|---|
| fixed length control field | 01950nab a2200217 4500 |
| 008 - CÓDIGOS DE INFORMACIÓN DE LONGITUD FIJA - INFORMACIÓN GENERAL | |
| Campo de control de longitud fija | 260224s2013 xxu ing |
| 041 ## - IDIOMA | |
| Idioma | Inglés |
| 245 00 - TITULO | |
| Título | Evaluation of the Onset of Flashover in Room Fire Experiments |
| 260 ## - PUBLICACION, DISTRIBUCION, ETC | |
| Lugar de publicación, distribución, etc. | |
| Nombre de publicador, distribuidor, etc. | |
| Fecha de publicación, distribución, etc. | oct. 2013 |
| 270 ## - FECHA DE CARGA | |
| Fecha de carga | 05/11/2013 ; 05/11/2013 |
| 300 ## - DESCRIPCION FISICA | |
| Otra extensión | 14 p. ; 891-905 |
| 520 ## - RESUMEN, ETC | |
| Resumen | Transcripción del resúmen realizada por el autor: Two series of full scale room fire tests comprising 16 experiments are used for a study of the onset of flashover. The fire loads were varied and represented seven different commercial applications and two non-combustible linings with significantly different thermal inertia were used. The test results showed that by lowering the thermal inertia and thereby lowering the heat loss from the room and at the same time increasing the thermal feedback, a thermal runaway occurred before significant fire spread; but only for objects composed of a mixture of plastic/rubber/textiles and wood/celluloses. In these cases the onset of thermal runaway was found to occur at room temperatures in the range 300°C to 420°C, supporting that the room temperature at the onset of thermal runaway is strongly dependent on the thermal inertia. It also shows that the onset of thermal runaway cannot in all cases implicitly be predicted by the traditional flashover temperature criterion of 500°C to 600°C. For fire loads composed of pure wood/celluloses the onset of flashover occurred about the same time as fire spread irrespectively of linings and at significantly higher room temperatures (725°C). This can be explained by flammability parameters making wood/celluloses less sensitive to thermal feedback. |
| 581 ## - ESTADO DE COLECCIÓN | |
| Estado de colección | 4 |
| 773 0# - CORRECCIÓN | |
| Título | Fire Technology |
| Partes relacionadas | 49 |
| 942 ## - DESC. DE MATERIAL | |
| Tipo de item KOHA | Artículo de Revista |
| 100 1# - RESPONSABLE PERSONAL | |
| Apellido, Nombre | Poulsen, Annemarie |
| 9 (RLIN) | 53599 |
| 100 1# - RESPONSABLE PERSONAL | |
| Apellido, Nombre | Jomaas, Grunde |
| 9 (RLIN) | 53600 |
| 100 1# - RESPONSABLE PERSONAL | |
| Apellido, Nombre | Bwalya, Alex |
| 9 (RLIN) | 40060 |
| Biblioteca propietaria | Biblioteca actual | Fecha de adquisición | Inventario | Total de préstamos | Inventario | Fecha de carga | Tipo de item KOHA |
|---|---|---|---|---|---|---|---|
| Biblioteca Alejandro Angel Bulgheroni | Biblioteca Alejandro Angel Bulgheroni | 06/03/2026 | 200060120 | 200060120 | 06/03/2026 | Artículo de Revista |