| 000 | 01522nab a2200181 4500 | ||
|---|---|---|---|
| 005 | 20260520000951.0 | ||
| 008 | 260224s2010 xxu | ||
| 245 | 0 | 0 | _aPerformance of different temperature sensors in standard fire resistance test furnaces |
| 260 |
_a _b _coct. 2010 |
||
| 270 | _a12/10/2010 ; 12/10/2010 | ||
| 300 | _a28 p. ; 853-881 | ||
| 520 | _aTranscripción del resumen del autor. Defining a methodology for measuring temperature in fire resistance furnaces is a challenge. This paper presents and discusses the performance of six different types of temperature sensors in wall and floor fire resistance furnaces namely: the ASTM E119 shielded thermocouples, ISO 834 plate thermometers, directional flame thermometers, bare-bead thermocouples, Inconel grounded and ungrounded sheathed thermocouples. The Inconel grounded and ungrounded sheathed thermocouples provided comparable results to those of the bear-bead thermocouples and are most suitable when a fast response time is desirable. Because of the fast response time and good durability, grounded and ungrounded junction thermocouples are well-suited for use in controlling the temperature in fire resistance standard test furnaces. The predicted and measured incident heat flux in furnaces controlled by either the bare-bead or grounded and ungrounded sheathed thermocouples are in good agreement. | ||
| 581 | _a4 | ||
| 773 | 0 |
_tFire Technology _g46 |
|
| 942 | _cARTICULO | ||
| 100 | 1 |
_aSultan, Mohamed A. _942114 |
|
| 999 |
_c177363 _d177363 |
||