245 0 0 _aExperimental investigation of an office fire with a partially impaired sprinkler system
260 _a
_b
_cjul. 2010
270 _a26/08/2010 ; 26/08/2010
300 _a31 p. ; 611-627
520 _aTranscripción del resumen del autor. In this work, an actual office fire with a partially impaired automatic sprinkler system was investigated. As per regulations, there were four sprinklers in this model office. In the research conducted here, the first three sprinklers were actuated without water supply, while the last sprinkler was supplied with water at the required operating pressure for a period of 30 min. The fire source, a burning plastic trash can filled with 0.5 kg of paper, burned the adjacent chair, desk, desktop computer, and then reached the interior wooden furniture. The results show that the single remaining sprinkler effectively controlled the fire spread for 30 min. The partially impaired sprinkler system does not completely extinguish the fire, but extends the available time for evacuation. Continuing the discharge from sprinklers is preferable since the heat release from the fire increased after water flow was terminated.
581 _a3
773 0 _tFire Technology
_g46
942 _cARTICULO
100 1 _aLai, Chi-Ming
_946631
100 1 _aHo, Ming-Chin
_946632
100 1 _aChen, Chiun-Hsun
_915184
999 _c176321