Experimental Study of Heat Transfer in Intumescent Coatings Exposed to Non-Standard Furnace Curves

By: Language: Inglés Publication details: mayo 2015Description: 16 p. ; 627-643 In: Fire Technology 51Summary: Transcripción del resúmen realizada por el autor: This paper reports the results of an experimental study on fire protection performance of intumescent coatings exposed to three non-standard fire curves. Intumescent coatings were applied to steel plates to make test specimens and, in total, furnace tests were performed on 36 specimens. The effective thermal conductivities of the intumescent coatings were calculated based on the measured steel and furnace temperatures. Scanning electron microscopy (SEM) tests were conducted to give some information on the difference in inner structure of intumescent char. Results of the experimental studies reveal that the fire protection performance of intumescent coating is highly dependent on the heating rate and maximum temperature of the fire condition. Different pore structures of the intumescent chars were obtained when intumescent coatings were subjected to fires with varied heating rates. The reaction steps of intumescent coating underwent depended on the maximum temperature of the fire condition. The consequence of this is changed expansion ratio and inner structure of intumescent char and then different effective thermal conductivity. When subjected to non-standard fire I, the reaction process of intumescent coating was incomplete and no "honeycomb" pore structure was observed; in comparison, the coating underwent complete reaction process and compact "honeycomb" pore structure was obtained when exposed to non-standard fire III; the maximum difference for representative values of effective thermal conductivities was up to 48.8%. In addition, due to the peculiar flame retardant mechanism of the intumescent coating, increasing the coating thickness does not always yield insulating property benefit.
Item type: Artículo de Revista
Holdings
Current library Status Barcode
Biblioteca Alejandro Angel Bulgheroni Not for loan 200061407

Transcripción del resúmen realizada por el autor: This paper reports the results of an experimental study on fire protection performance of intumescent coatings exposed to three non-standard fire curves. Intumescent coatings were applied to steel plates to make test specimens and, in total, furnace tests were performed on 36 specimens. The effective thermal conductivities of the intumescent coatings were calculated based on the measured steel and furnace temperatures. Scanning electron microscopy (SEM) tests were conducted to give some information on the difference in inner structure of intumescent char. Results of the experimental studies reveal that the fire protection performance of intumescent coating is highly dependent on the heating rate and maximum temperature of the fire condition. Different pore structures of the intumescent chars were obtained when intumescent coatings were subjected to fires with varied heating rates. The reaction steps of intumescent coating underwent depended on the maximum temperature of the fire condition. The consequence of this is changed expansion ratio and inner structure of intumescent char and then different effective thermal conductivity. When subjected to non-standard fire I, the reaction process of intumescent coating was incomplete and no "honeycomb" pore structure was observed; in comparison, the coating underwent complete reaction process and compact "honeycomb" pore structure was obtained when exposed to non-standard fire III; the maximum difference for representative values of effective thermal conductivities was up to 48.8%. In addition, due to the peculiar flame retardant mechanism of the intumescent coating, increasing the coating thickness does not always yield insulating property benefit.

3



Instituto Argentino del Petróleo y del Gas
Maipú 639 (C1006ACG) – Buenos Aires – Argentina
Tel: (54 11) 5277 IAPG (4274)
Lu - Vie 11 a 17 hs
Mail: biblio@iapg.org.ar


Copyright © 2026, Instituto Argentino del Petróleo y del Gas, todos los derechos reservados.

Protección de datos personales