Characteristics of Nuclear Facility Waste Bag Fires

By: Language: Inglés Publication details: ene. 2015Description: 23 p. ; 129-152 In: Fire Technology 51Summary: Transcripción del resúmen realizada por el autor: Waste bags from nuclear facilities filled with plastic personal protective equipment were tested to measure their fire hazard. Heat release rate (HRR), smoke yield and incident heat flux from waste bag fires were measured in a room/corner test apparatus. Three different size bags were tested in the corner of the room in order to check the effect of waste bag size. Full size waste bags were tested in the three different locations: in the center, in the corner and against the back wall of the room in order to check the effect of location. Bag fires can produce high HRRs (~800 kW) indicating that special caution is needed for waste bag management in nuclear facilities. Different size bags burn in a similar manner which allows a simple analytical tool to be developed to estimate transient HRR. In addition to the analytical tool, smoke yield and heat flux data can be used to simulate the waste bag fires and to validate fire model simulations.
Item type: Artículo de Revista
Holdings
Current library Status Barcode
Biblioteca Alejandro Angel Bulgheroni Not for loan 200061397

Transcripción del resúmen realizada por el autor: Waste bags from nuclear facilities filled with plastic personal protective equipment were tested to measure their fire hazard. Heat release rate (HRR), smoke yield and incident heat flux from waste bag fires were measured in a room/corner test apparatus. Three different size bags were tested in the corner of the room in order to check the effect of waste bag size. Full size waste bags were tested in the three different locations: in the center, in the corner and against the back wall of the room in order to check the effect of location. Bag fires can produce high HRRs (~800 kW) indicating that special caution is needed for waste bag management in nuclear facilities. Different size bags burn in a similar manner which allows a simple analytical tool to be developed to estimate transient HRR. In addition to the analytical tool, smoke yield and heat flux data can be used to simulate the waste bag fires and to validate fire model simulations.

1



Instituto Argentino del Petróleo y del Gas
Maipú 639 (C1006ACG) – Buenos Aires – Argentina
Tel: (54 11) 5277 IAPG (4274)
Lu - Vie 11 a 17 hs
Mail: biblio@iapg.org.ar


Copyright © 2026, Instituto Argentino del Petróleo y del Gas, todos los derechos reservados.

Protección de datos personales