Image from Google Jackets

Investigation on the performance of fire detection systems for tunnel applications Part 2: Full-scale experiments under longitudinal airflow conditions

By: Publication details: ene. 2011Description: 30 p. ; 191-220 In: Fire Technology 47Summary: Transcripción del resumen del autor. This paper presents the results of the full-scale experiments conducted in a laboratory tunnel facility under longitudinal airflow conditions and in the Carré-Viger Tunnel. The performance of nine fire detection systems representing five types of the fire detection technologies for road tunnel applications was investigated using representative tunnel fire scenarios. The changes in fire characteristics caused by longitudinal airflow, such as fuel burning time, fire growth rate, temperatures and smoke spread in the tunnel, were measured and analyzed. The experimental results showed that the detection time of the fire detection systems under longitudinal airflow conditions could be increased or decreased, depending on the fuel type, fire size and location, airflow velocity and detection method.
Item type: Artículo de Revista
Holdings
Current library Status Barcode
Biblioteca Alejandro Angel Bulgheroni Not for loan 200056080

Transcripción del resumen del autor. This paper presents the results of the full-scale experiments conducted in a laboratory tunnel facility under longitudinal airflow conditions and in the Carré-Viger Tunnel. The performance of nine fire detection systems representing five types of the fire detection technologies for road tunnel applications was investigated using representative tunnel fire scenarios. The changes in fire characteristics caused by longitudinal airflow, such as fuel burning time, fire growth rate, temperatures and smoke spread in the tunnel, were measured and analyzed. The experimental results showed that the detection time of the fire detection systems under longitudinal airflow conditions could be increased or decreased, depending on the fuel type, fire size and location, airflow velocity and detection method.

1



Instituto Argentino del Petróleo y del Gas
Maipú 639 (C1006ACG) – Buenos Aires – Argentina
Tel: (54 11) 5277 IAPG (4274)
Lu - Vie 11 a 17 hs
Mail: biblio@iapg.org.ar


Copyright © 2026, Instituto Argentino del Petróleo y del Gas, todos los derechos reservados.

Protección de datos personales